Key data
| Fluid | R404A (blend of R125, R143a and R134a, 44/52/4 % by mass) |
|---|---|
| CAS number | — |
| Molar mass | 97.604 g/mol |
| Critical temperature | 72.12 °C (345.27 K) |
| Critical pressure | 37.35 bar (3.735 MPa) |
| Critical density | 482.2 kg/m³ |
| Lowest temperature of the equation | -73.15 °C |
| Bubble / dew point at 1 atm | -46.22 °C / -45.47 °C |
| Equation of state | Lemmon (2003), Pseudo-Pure Fluid Equations of State for the Refrigerant Blends R-410A, R-404A, R-507A, and R-407C, Int. J. Thermophys. 24, 991-1006. doi:10.1023/A:1025048800563 |
| Viscosity correlation | Geller (2000), Viscosity of Mixed Refrigerants R404A, R407C, R410A, and R507A. |
| Thermal conductivity correlation | Geller et al. (2001), Thermal Conductivity of the Refrigerant mixtures R404A, R407C, R410A, and R507A, Int. J. Thermophys. 22, 1034-1043. doi:10.1023/A:1010691504352 |
| Reference for h and s | IIR convention: h = 200 kJ/kg and s = 1 kJ/(kg·K) for the saturated liquid at 0 °C |
Reading the diagrams of R404A
- P-h (pressure–enthalpy): the usual chart for refrigeration cycles. Heat exchanged at constant pressure is a horizontal distance; an ideal compression follows an isentrope.
- P-T: the saturation line separates liquid and vapour and ends at the critical point (72.12 °C, 37.35 bar).
- T-s and h-s (Mollier): the two-phase dome, with the bubble line (saturated liquid) on its left and the dew line (saturated vapour) on its right.
- Vapour or gas? Both words describe the gaseous state. Below the critical temperature of R404A (72.12 °C), its gaseous phase is called a vapour: compression alone can condense it. Above that temperature it is called a gas, and a supercritical fluid when the pressure is also above the critical pressure (37.35 bar). The dash-dot lines of the diagrams mark these limits.
The selected state is kept when you change diagram, and the address of the page records it: copy the link to share a state.
Key facts about R404A
The critical point of R404A is at 72.12 °C and 37.35 bar. At atmospheric pressure it starts boiling at -46.22 °C (bubble point) and is fully vaporised at -45.47 °C (dew point): a temperature glide of 0.75 K. Its mean molar mass is 97.604 g/mol.
Method and limits
Properties are computed with the equation of state of Lemmon (2003), using the coefficients published in the open-source library CoolProp. The site's own engine reproduces CoolProp's values to better than one part in a hundred million on the tested states.
- Viscosity and thermal conductivity come from the correlations of Geller (2000) and Geller et al. (2001), as implemented in CoolProp; they are shown for single-phase states only.
- Solid phases are not represented: below the triple point or at very high pressure near the melting line, results do not describe a real state.
- R404A is a blend modelled as a single pseudo-pure fluid: inside the two-phase region, temperature and properties are interpolated linearly between the bubble and dew points, as in CoolProp.
See the credits and licences page for the sources.