How to read the psychrometric chart
The horizontal axis is the dry-bulb temperature (an ordinary thermometer); the vertical axis is the humidity ratio, the mass of water vapour carried by one kilogram of dry air. The orange curve is saturation (100 % relative humidity): air cannot hold more vapour, and above it the excess condenses as fog or dew.
- Solid curves: constant relative humidity, from 10 to 90 %.
- Dotted oblique lines: constant enthalpy, in kJ per kg of dry air. They are close to the lines of constant wet-bulb temperature.
- Dashed steep lines: constant specific volume, in m³ per kg of dry air.
- Heating or cooling without adding or removing water is a horizontal line. Cooling below the dew point condenses water: the point then follows the saturation curve (dehumidification). Evaporative (adiabatic) humidification follows a line of nearly constant enthalpy.
Example computed by this page: at 20 °C and 50 % relative humidity (1013.25 hPa), the humidity ratio is 7.26 g/kg, the enthalpy 38.6 kJ/kg, the wet-bulb temperature 13.8 °C, the dew point 9.3 °C and the specific volume 0.840 m³/kg.
Method and range
Humid air is treated as an ideal mixture of dry air and water vapour, with the relations of the ASHRAE Handbook – Fundamentals (chapter “Psychrometrics”) for the humidity ratio, enthalpy, specific volume and wet-bulb temperature. The saturation pressure comes from IAPWS-IF97 above 0 °C and from the IAPWS equation for ice below 0 °C, as on the dew-point tab.
The enhancement factor (non-ideal behaviour of the mixture) is neglected: compared with CoolProp's real-gas model, the humidity ratio differs by less than 1 %. The chart covers −10 to 50 °C and is redrawn for the total pressure you enter (useful at altitude).