The four processes
- 1→2 Compressor Slightly superheated vapour is compressed from the evaporating to the condensing pressure. Work: w = h₂ − h₁; a real compressor (isentropic efficiency below 100 %) needs more work and discharges hotter vapour.
- 2→3 Condenser At high pressure the vapour is cooled (desuperheating), condenses, then the liquid is subcooled. Heat rejected: q_H = h₂ − h₃ — the useful heat of a heat pump.
- 3→4 Expansion valve Throttling at constant enthalpy (h₄ = h₃): a vertical line on the P-h diagram. Pressure and temperature drop and part of the liquid flashes into vapour.
- 4→1 Evaporator The cold liquid–vapour mixture evaporates at low pressure, taking q_L = h₁ − h₄ from the cooled space, then is slightly superheated before returning to the compressor.
Coefficient of performance (COP)
COP in cooling = q_L / w; COP in heating = q_H / w = COP cooling + 1. The upper limit is the Carnot COP, T_evap / (T_cond − T_evap) for cooling (temperatures in kelvin): it falls quickly when the temperature lift grows, which is why a heat pump is less efficient in very cold weather.
The enthalpy differences are read directly on the horizontal axis of the P-h diagram: this is why refrigeration engineers use it so much.
Superheat, subcooling and blends
- Superheat at the evaporator outlet makes sure no liquid reaches the compressor.
- Subcooling at the condenser outlet avoids vapour before the expansion valve and increases the cooling effect.
- For blends (R410A, R407C, R404A) the temperature changes during evaporation and condensation (glide). The evaporating and condensing temperatures entered here are dew-point temperatures, as in the AHRI rating standards.
Example: R134a between 1.4 and 8 bar (ideal cycle, saturated vapour and liquid) gives a COP of 3.97, as in the classic textbook example (Çengel & Boles, Example 11-1), reproduced by the site's tests.
Method
Refrigerant properties from the site's engine (reference equations of state exported from CoolProp 8.0.0, checked against it).