Vapour-compression refrigeration cycle

This is the cycle of refrigerators, air conditioners and heat pumps. Choose the refrigerant, the evaporating and condensing temperatures, the superheat, the subcooling and the compressor efficiency: the cycle is drawn on the pressure–enthalpy and temperature–entropy diagrams, with its COP.

Parameters

Results

COP (cooling)3.13
COP (heating, heat pump)4.13
Cooling effect (4→1)145.0kJ/kg
Compressor work (1→2)46.3kJ/kg
Heat rejected at the condenser (2→3)191.3kJ/kg
Discharge temperature (2)61.9°C
Evaporating pressure2.006bar
Condensing pressure10.17bar
Pressure ratio5.07
Quality at the evaporator inlet (4)0.317
Carnot COP (cooling)5.26

States of the cycle

PointPressurebarTemperature°CEnthalpykJ/kgEntropykJ/(kg·K)Quality x
12.006-5.00396.931.7494—
210.16661.88443.211.7845—
310.16637.00251.941.1761—
42.006-10.00251.941.19860.317
Pressure–enthalpy diagram · Open the interactive diagram
Temperature–entropy diagram · Open the interactive diagram

The four processes

  1. 1→2 Compressor Slightly superheated vapour is compressed from the evaporating to the condensing pressure. Work: w = h₂ − h₁; a real compressor (isentropic efficiency below 100 %) needs more work and discharges hotter vapour.
  2. 2→3 Condenser At high pressure the vapour is cooled (desuperheating), condenses, then the liquid is subcooled. Heat rejected: q_H = h₂ − h₃ — the useful heat of a heat pump.
  3. 3→4 Expansion valve Throttling at constant enthalpy (h₄ = h₃): a vertical line on the P-h diagram. Pressure and temperature drop and part of the liquid flashes into vapour.
  4. 4→1 Evaporator The cold liquid–vapour mixture evaporates at low pressure, taking q_L = h₁ − h₄ from the cooled space, then is slightly superheated before returning to the compressor.

Coefficient of performance (COP)

COP in cooling = q_L / w; COP in heating = q_H / w = COP cooling + 1. The upper limit is the Carnot COP, T_evap / (T_cond − T_evap) for cooling (temperatures in kelvin): it falls quickly when the temperature lift grows, which is why a heat pump is less efficient in very cold weather.

The enthalpy differences are read directly on the horizontal axis of the P-h diagram: this is why refrigeration engineers use it so much.

Superheat, subcooling and blends

Example: R134a between 1.4 and 8 bar (ideal cycle, saturated vapour and liquid) gives a COP of 3.97, as in the classic textbook example (Çengel & Boles, Example 11-1), reproduced by the site's tests.

Method

Refrigerant properties from the site's engine (reference equations of state exported from CoolProp 8.0.0, checked against it).

Course refresher: thermodynamic properties